Appendix 3- Parameter Cross Reference
PL.F7.05 Page
41
of 54
GPD506/P5 Parameter
F7 Parameter
Param
No.
Nxxx
Parameter
Name
Description or Selection
Description or Selection
Parameter
Name
Param.
No.
(con’t)
037
Multi-function contact input 2
(terminal S3)
Set range: 2-28
(It is the same as constant n036)
Open = Only using monitor U1-01 can
be changed.
1C: Trim Control Increase
Closed = Increase frequency reference
By value in d4-02.
Open = Return to normal frequency
reference.
Not effective when “multi-step speed 1
to 4” input is closed. Must be used in
conjunction with Trim Ctrl Decrease.
1D: Trim Control Decrease
Closed = Decrease frequency reference
by value in d4-02
Open = Return to normal frequency
reference.
Not effective when using d1-01 thru
d1-16 as frequency reference. Must be
used in conjunction with Trim Ctrl
Increase.
1E: Reference Sample Hold
Analog frequency reference is sampled
then held at time of input closure.
20: External Fault, Normally Open, Always
Detected, Ramp To Stop
21: External Fault, Normally Closed,
Always Detected, Ramp To Stop
22: External Fault, Normally Open, During
Run, Ramp To Stop
23: External Fault, Normally Closed,
During Run, Ramp To Stop
24: External Fault, Normally Open, Always
Detected, Coast To Stop
25: External Fault, Normally Closed,
Always Detected, Coast To Stop
26: External Fault, Normally Open, During
Run, Coast To Stop
27: External Fault, Normally Closed,
During Run, Coast To Stop
28: External Fault, Normally Open, Always
Detected, Fast-Stop
29: External Fault, Normally Closed,
Always Detected, Fast-Stop
2A: External Fault, Normally Open, During
Run, Fast-Stop
2B: External Fault, Normally Closed,
During Run, Fast-Stop
2C: External Fault, Normally Open,
Always Detected, Alarm Only
2D: External Fault, Normally Closed,
Always Detected, Alarm Only
2E: External Fault, Normally Open, During
Run, Alarm Only
2F: External Fault, Normally Closed,
During Run, Alarm Only
30: PID integral reset
Closed = Set integrator value to 0.
31: PID integral hold
Closed = Hold integrator at its present
level.
32: Multi-Step Reference 4
Based on the status of Multi-Step
Reference 1 to 4 (d1-16).
34: PID Soft Starter Cancel
Closed = b5-17 is ignored.
35: PID Input (Error) Polarity Change
Closed = PID error signal polarity is
reversed (1 to -1 or -1 to 1).
60: DC Injection Braking
Closed = Apply DC injection current as
set in parameter b2-02.
Multi-Function Digital Input
Terminal S3 Function
Selection
H1-01