Appendix 3- parameter cross reference, Parameter name, Description or selection – Yaskawa GPD 506/P5 to F7 User Manual

Page 45

background image

Appendix 3- Parameter Cross Reference

PL.F7.05 Page

45

of 54

GPD506/P5 Parameter

F7 Parameter

Param

No.

Nxxx

Parameter

Name

Description or Selection

Description or Selection

Parameter

Name

Param.

No.

041

contact output 1
(terminal MA-MB-MC)

(when in torque control)
Closed = When motor frequency is at
the speed limit value when running in
torque control.
33: Zero-Servo Complete
Closed = When Zero Servo is complete
within the b9-02 zero servo completion
width.
37: During Operation
Closed = When Drive is operating
(except during baseblock or DC
braking).
38: Drive Enable
Closed = When the Drive enable input
is active.

Terminal M1-M2 Function
Selection

H2-01

042

Multi-function
contact output 2
(terminal M1-M2)

It is the same as constant n041.

Same selections as H2-01

Terminal M3-M4 Function
Selection

H2-02

043

Analog input select













Note: (n084 ≠ 0) FV term = master speed, FI terminal = feedback. Memobus
register 80H=0 does not set 3 & 4.

-

044

Terminal FI signal Level
Selection

0: The FI terminal inputs 0-10V.
(Jumper J1 is cut)
1: The FI terminal inputs 4-20mA.

Selects the signal level of terminal A2.
0: 0 to 10Vdc (switch S1-2 must be in the
OFF position).
1: -10 to +10Vdc (switch S1-2 must be in
the OFF position).
2: 4 to 20mA (switch S1-2 must be in the
ON position)

Terminal A2 Signal Level
Selection

H3-08

045

Frequency Reference
Retention

1: The holding frequency reference is not
memorized.
0: The holding frequency reference is
memorized and stored in n024

This parameter is used to retain the held
frequency reference in U1-01 (d1-01) when
power is removed. This function is
available when the multi-function inputs
“accel/decel ramp hold” or “up/down”
commands are selected
(H1-XX = A or 10 and 11).
0: Disabled
1: Enabled

Frequency Reference Hold
Function Selection

d4-01

046

Frequency Ref
Loss selection

0: No detection
1: Continue running at n047 setting

The frequency reference is considered lost
when reference drops 90% or more of its
current value in less than 400ms.
0: Normal Operation - Drive will run at the
frequency reference.
1: Run at L4-06 PrevRef - Drive will run at
the percentage set in L4-06 of the
frequency reference level at the time
frequency reference was lost.

Frequency Reference Loss
Detection Selection

L4-05

047

Frequency Ref
when frequency reference is
lost

Set unit: 1% and set range: 0-100%

0 to 100.0
If the frequency reference loss function is
enabled (L4-05=1) and frequency reference
is lost, the Drive will run at a reduced
frequency reference determined by the
following formula:
Fref=Fref at time of loss * L4-06.

Frequency Reference Level at
Loss Frequency

L4-06

048

Terminal FV gain

Set unit: 1% and set range: 0 to 200%

0.0 to1000.0
Sets the output level when 10V is input, as
a percentage of the maximum output

Terminal A1 Gain Setting

H3-02

Value Terminal FV

FI terminal

Note

0

Master speed

Auxiliary

FV/FI switch enabled

1

Auxiliary

Master speed

FV/FI switch enable

2

Fault reset

Master speed

FV/FI switch disabled

3

Master speed

N

monitor

input

FV/FI switch disabled

4

Fault reset

N

monitor input

FV/FI switch disabled