Nec hp ratings for 230v normal duty models – Yaskawa GPD 506/P5 to F7 User Manual
Page 27

Product Transition Guide
Appendix 1 –Ratings and Heat Loss Comparison
PL.F7.05 Page
27
of 54
NEC HP Ratings for 230V Normal Duty Models
GPD506/P5 230V Models
F7 240V Models
Variable
Torque
(n116=1)
Normal Duty
(C6-01=2)
NEC
HP
230V
NEC
Amps
GPD506/P5
Model
CIMR-P5U
Output
Amps
Fc
kHz
Overload%
VT
1 minute
F7
Model
CIMR-F7U
Output
Amps
Fc
kHz
Overload %
ND
1 minute
0.5 2.2 20P41 3.2
15 120
0.75 3.2
20P41 3.6 10 107
1 4.2 20P71 6.0
15 120 20P71 4.6 10 107
1.5 6
2 6.8 21P51 8.0
15 120
21P51 7.8 10 108
3 9.6 22P21 11
15 120 22P21 10.8 8 107
5 15.2 23P71 17.5
15 120 23P71 16.8 10 107
7.5 22 25P51 27
10 120 25P51 23 15 120
10 28 27P51 36
10 120 27P51 31 15 102
15 42 20111 54
10 120 20111 46.2 8 117
20 54
20151 59.4 10 117
25 68 20151 68
10 120 20181 74.8 10 114
30 80 20181 80
15 120 20221 88 10 116
40 104 20221 104
15 120 20301 115 10 120
50 130 20301 130
10 120
60 154 20371 160
10 120
20371 162 5 107
75 192 20451 192
10 120 20451 192 5 113
20551 215 8 120
100 248 20551 248 8
120
125 312 20751 312 8
120
20751 312 2 109
150 360
- -
- - 20901 360 2 115
150 360
- -
- - 21100 415 2 120