Mop min percent p2-04 = 0, Mop rst percent p2-05 = 0 – Yaskawa G5 Eliminator User Manual
Page 24

Date: 07/01/04, Rev: 04-07
Page 24 of 27
TM.G5SW.015
MOP UP or 83 MOP DOWN is energized for 5ms. Maintaining this input will result in output 25
changing at this rate per second. Refer to section 2.1.2.
MOP Max Percent
P2-03 = 100 %
P2-03
MOP
Maximum
Percentage
B B B B
The MOP Max Percent sets the maximum MOP value possible for outputs 25 and 26. Refer to
section 2.1.2.
MOP Min Percent
P2-04 = 0 %
P2-04
MOP
Minimum
Percentage
B B B B
The MOP Min Percent sets the minimum MOP value possible for outputs 25 and 26. Refer to
section 2.1.2.
MOP Rst Percent
P2-05 = 0 %
P2-05
MOP
Reset
Percentage
B B B B
The MOP Rst Percent is the value that outputs 25 and 26 are reset to when the multi-function
input assigned to 84 MOP RESET is energized. Refer to section 2.1.2.
MOP Step Rate
P2-06 = 0.00 %
P2-06
MOP
Step
Rate
B B B B
The MOP Step Rate is the number that will be added to or subtracted from the current value of
output 26 when the multi-function input assigned to 82 MOP UP or 83 MOP DOWN is energized
for 5ms. Each transition of either input will result in one step. Refer to section 2.1.2.
Setting Range:
0 to 1000 %
Factory Default:
100 %
Modify During Run:
Yes
Modbus Address:
0592H
Setting Range:
-1000 to 100 %
Factory Default:
0 %
Modify During Run:
Yes
Modbus Address:
0593H
Setting Range:
-1000 to 1000 %
Factory Default:
0 %
Modify During Run:
Yes
Modbus Address:
0594H
Setting Range:
0.00 to 100.00
Factory Default:
0.00
Modify During Run:
Yes
Modbus Address:
0595H