The drive’s analog outputs can be connected to monitor U1-50 and U1-51. This feature must be
setup. The displayed value will be sent to the associated analog output. Setting the connected
analog output gain to 10 will provide the actual value connected to the monitor. The analog
output will operate within the defined range. The gain and bias parameters can be used to scale
the analog output.
Function
Information
Setup
Monitor 1 (U1-50)
H4-01 or H4-04 = 50: Case Monitor 1
Monitor 2 (U1-51)
Information can be passed to analog output terminals 21
and 23
H4-01 or H4-04 = 51: Case Monitor 2
2.3.6 Write Memory
Write Memory functions allow values to be stored into memory. The last value input is stored in
running memory not NVRAM. This number can be read using the corresponding Read Memory
function. This function serves as a means to end and store the final value of a function’s output.
This number value can be reintroduce into the control logic where needed by using the Read
Memory function. If the input of the Read Memory function is used before the corresponding
Write Memory function in the configuration sequence the value read will be from the previous
scan. This feature can be used to determine the change from scan to scan.
Figure 2.3.6
Write
Memory 1
44
Write
Memory 2
45