Scale multiplier p1-08 = 0, Scale divisor p1-09 = 0, Scale bias p1-10 = 0 – Yaskawa G5 Eliminator User Manual
Page 23

Date: 07/01/04, Rev: 04-07
Page 23 of 27
TM.G5SW.015
Scale Multiplier
P1-08 = 0
P1-08
Scale
Multiplier
B B B B
The Scale Multiplier number is multiplied times the value of input 60. Refer to section 2.2.5.
Scale Divisor
P1-09 = 0
P1-09
Scale
Divisor
B B B B
The Scale Divisor is the number divided into the product of the scale multiplication. Refer to
figure 2.2.5.
Scale Bias
P1-10 = 0
P1-10
Scale
Bias
B B B B
The Scale Bias is the number that will be added to the value of the scale calculation to offset the
value of output 61 up or down. Refer to section 2.2.5.
Max Pulses In
P2-01 = 30720
P2-01
Max
Pulses
Input
B B B B
The Max Pulses In is the number that equals the input pulse rate per second that will result in
100 % inverter output. Refer to section 2.1.4.
Example: 30720 = (1800 rpm X 1024 encoder pulses per rev) / 60 sec (30720 is the default)
MOP Rate / Sec
P2-02 = 0.00 %
P2-02
MOP Rate / Second
B
B
B
B
The MOP Rate / Sec sets the rate of MOP change for output 25. This number will be added to
or subtracted from the current value of output 25 when the multi-function input assigned to 82
Setting Range:
-9999 to 9999
Factory Default:
0
Modify During Run:
Yes
Modbus Address:
0587H
Setting Range:
-9999 to 9999
Factory Default:
0
Modify During Run:
Yes
Modbus Address:
0588H
Setting Range:
-9999 to 9999
Factory Default:
0
Modify During Run:
Yes
Modbus Address:
0589H
Setting Range:
0 to 65535
Factory Default:
30720
Modify During Run:
Yes
Modbus Address:
0590H
Setting Range:
0.01 to 100.00 %
Factory Default:
0.00 %
Modify During Run:
Yes
Modbus Address:
0591H