7 troubleshooting – Yaskawa Option PG-F3 Motor Encoder Feedback User Manual
Page 37

7 Troubleshooting
YASKAWA ELECTRIC TOBP C730600 51F 1000-Series Option PG-F3 Installation Manual
37
Digital Operator Display
Fault Name
oFC01
Option Connection Error at drive port CN5-C
Cause
Possible Solution
Option at drive port CN5-C was
changed during run.
Switch the power off and reconnect the option.
Digital Operator Display
Fault Name
oFC50
PG Encoder Option A/D Conversion Error
Error with the A/D conversion level (VCC level), or A/D conversion timed out.
Cause
Possible Solution
The option is damaged.
Replace the option.
Digital Operator Display
Fault Name
oFC51
PG Encoder Option Analog Circuit Error
Incorrect signal level (+2.5 V signal)
Cause
Possible Solution
The option is damaged.
Replace the option.
Digital Operator Display
Fault Name
oFC52
PG Encoder Communication Timeout
Serial encoder timed out waiting to receive data
Cause
Possible Solution
PG encoder wiring is incorrect.
Correct the wiring.
PG encoder cable is
disconnected.
Reconnect the cable.
F1-50 (Encoder selection) is
incorrect.
Set F1-50 (Encoder selection) according to the encoder connected to the drive.
Digital Operator Display
Fault Name
oFC53
PG Encoder Communication Data Error
Serial encoder CRC checksum error
Cause
Possible Solution
PG encoder wiring is incorrect.
Correct the wiring.
PG encoder cable is
disconnected.
Reconnect the cable.
Digital Operator Display
Fault Name
oFC54
PG Encoder Error
Alarm reading EnDat absolute position data from the PG encoder
(OR flag from EnDat error for overvoltage, undervoltage, etc.)
Cause
Possible Solution
Power supply to PG encoder is
wired incorrectly.
Correct the wiring.