6 Related Parameters

6

Related Parameters

The following parameters set the drive for operation with the option. Set parameters as

needed. Parameter setting methods can be found in the drive Quick Start Guide or Technical

Manual.

Table 10

Related Parameters

No.

(Addr. Hex)

Name

Description

Control

Mode

Values

A1-02

(102)

Control Method
Selection

0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
5: Open Loop Vector Control for PM
6: Advanced Open Loop Vector Control for PM
7: Closed Loop Vector Control for PM
Note: Set to 7 when using PG-F3.

All Modes

Default:

<1>

Range:

<1>

F1-01

(380)

<2>

PG 1 Pulses per
Revolution

Sets the signal periods per revolution to be read from
the pulse generator.

CLV
CLV/PM

Default:

<1>

Min:

<1>

Max:

<1>

F1-02

(381)

PG Feedback
Loss Operation
Selection

Sets the stopping method after PG disconnect (PGo).
0: Ramp to stop (decelerates at time set to C1-02)
1: Coast to stop
2: Fast Stop (decelerates at the time set to C1-09)
3: Continue running
4: No alarm display
NOTICE: Due to potential damage to the motor and
machinery, only use settings 3 and 4 under special
circumstances.

CLV
CLV/PM

Default: 1
Range:

<1>

F1-03

(382)

PG Overspeed
Operation
Selection

Sets the stopping method after detecting overspeed.
0: Ramp to stop (decelerates at time set to C1-02)
1: Coast to stop
2: Fast Stop (decelerates at the time set to C1-09)
3: Continue running
NOTICE: Due to potential damage to the motor and
machinery, do not use the "Continue running" setting
except under special circumstances.

CLV
CLV/PM

Default: 1
Range: 0 to 3

F1-04

(383)

PG Deviation
Operation
Selection

0: Ramp to stop (decelerates at time set to C1-02)
1: Coast to stop
2: Fast Stop (decelerates at the time set to C1-09)
3: Continue running
NOTICE: Due to potential damage to the motor and
machinery, do not use the "Continue running" setting
except under special circumstances.

CLV
CLV/PM

Default:

<1>

Range: 0 to 3

F1-05

(384)

PG 1 Rotation

0: Forward = A pulse leads
1: Forward = B pulse leads

CLV
CLV/PM

Default:

<1>

Range: 0, 1