6 Related Parameters

YASKAWA ELECTRIC TOBP C730600 51F 1000-Series Option PG-F3 Installation Manual

33

F1-06

(385)

PG 1 Ratio for
PG Pulse
Monitor

Sets the division ratio for PG encoder pulse output.
Set as a three-digit number: x is the first digit, y is the
second digit, and z is the third digit:
When using the PG-F3 option, the drive disregards
the value set for "x", and uses the formula 1/yz to
determine the division rate for the pulse generator.
The setting range is 1/32 : 1.

CLV
CLV/PM

Default: 1
Min: 1
Max: 132

F1-08

(387)

PG Overspeed
Level

Sets the level for detecting overspeed as a percentage
of the maximum output frequency.

CLV
CLV/PM

Default: 115
Min: 0
Max: 120

F1-09

(388)

Overspeed Det.
Time

Sets the time required for the motor to exceed the
level set in F1-08 to trigger a fault.

CLV
CLV/PM

Default: 0.0
Min: 0.0
Max: 2.0

F1-10

(389)

Excessive Speed
Deviation Det.
Level

Sets the degree of speed deviation to trigger a dEv
fault. Set as a percentage of the maximum output
frequency.

CLV
CLV/PM

Default: 10
Min: 0
Max: 50

F1-11
(38A)

Excessive Speed
Deviation Det.
Time

Sets the time required for a speed deviation situation
to trigger a fault.

CLV
CLV/PM

Default: 0.5
Min: 0.0
Max: 10.0

F1-14
(38D)

PG Disconnect
Det. Time

Sets the time in seconds for PG encoder disconnect to
be detected.

CLV
CLV/PM

Default: 2.0
Min: 0.0
Max: 10.0

F1-18

(3AD)

Reverse
Rotation Det.
for PG 1

0: Disabled
n: Number of times a dv3 situation must be detected
to trigger a fault.

CLV/PM

Default: 10
Min: 0
Max: 10

F1-19

(3AE)

Reverse
Rotation Det.
for PG 1

0: Disabled
n: Number of times a dv4 situation must be detected
to trigger a fault.

CLV/PM

Default: 128
Min: 0
Max: 5000

F1-20

(3B4)

PG 1 Hardware
Disconnect

0: Disabled. No fault if the connection is lost.
1: Enabled. Fault if connection is lost.

CLV
CLV/PM

Default: 1
Range: 0, 1

F1-50
(3D2)

Encoder
Selection

0: EnDat 2.1/2.2 Serial+Sin/Cos
1: EnDat 2.2 Serial only
2: HIPERFACE

CLV/PM

Default: 0
Range: 0 to 2

F1-51
(3D3)

PGoH Detection
Level

Sets the level for detecting a PG Hardware Fault
(PGoH). Set as a percentage of

.

CLV/PM

Default: 80
Min: 1
Max: 100

No.

(Addr. Hex)

Name

Description

Control

Mode

Values

Sin

θ

2

+ Cos

θ

2