9 Fault Diagnosis and Possible Solutions

YASKAWA ELECTRIC TOBP C730600 45B 1000-Series Option SI-S3 Installation Manual

33

Digital Operator Display

Fault Name

EF0

External Fault Input from CANopen Option

The alarm function for an external device has been triggered.

Cause

Possible Solution

An external fault is being sent from
the upper controller (PLC).

⇒ Remove the cause of the external fault.

⇒ Reset the external fault input from the upper controller (PLC) device.

Problem with the upper controller
(PLC) program.

⇒ Check the program used by the upper controller (PLC) and make the
appropriate corrections.

Digital Operator Display

Fault Name

oFA00

Option Card Fault at Connector CN5-A

The drive dose not support the option board plugged into port CN5-A.

Cause

Possible Solution

Non-compatible option connected to
the drive.

⇒ Check the drive option board compatibility. Replace the option card if the
fault persists even though the drive should support it.

Digital Operator Display

Fault Name

oFA01

Option Card Fault at Connector CN5-A

Option card is not properly connected.

Cause

Possible Solution

Problem with the connectors between
the drive and CANopen Option.

⇒ Turn the power off and check the connectors between the drive and
CANopen Option.

Digital Operator Display

Fault Name

to

oFA30 to oFA43

Option Card Fault at Connector CN5-A

Communication ID error

Cause

Possible Solution

Option card hardware fault

⇒ Replace the CANopen Option. Contact Yaskawa for assistance.