The following parameters are displayed in the parameter list but cannot be modified:

U

DC

WindStart

V

1 ... 800

330

U

DC

WindStart represents the lowest

point of the function (please read more
about this topic in chapter 6 "Turbine
operation” (page 33)
). (only possible in
Turbine mode!)

Usoll-Konst /
Vconst-
Setpiont

V

250

...600

600

Desired DC voltage for constant
operational voltage. These parameters
are only important when the
"Betriebsart" parameter is set to U-
Konst.

U

PV

Start

V

250 ... 600

300

U

PV

Start is the parameter defining the

voltage at which the Windy Boy is
capable of connecting to the system.
180 V is the recommended voltage for
the Windy Boy 5000 and the Windy
Boy 6000. Reducing this voltage
parameter can lead to numerous
unnecessary connection attempts.
Increasing this voltage parameter can
lead to energy losses since the Windy
Boy does not immediately connect to the
system.

Name

Unit

Value range

(WB5000/

6000)

Factory
settings

(WB5000/

6000)

Description

Plimit

W

5000 / 6000

5000 / 6000

Upper limit for AC output power

SMA-SN

Serial number of the Windy Boy 5000
/ 6000

Software-BFR /
Firmware-BFR

Firmware version of the operation
control unit (BFR)

Software-SRR /
Firmware-SRR

Firmware version of the current control
unit (SRR)

Name Unit

Value

range

(WB 5000 /
WB 6000)

Factory
settings
(WB 5000
/WB
6000)

Description