SMA WB 5000 User Manual
Page 35
SMA
Technology AG
Turbine operation
Operating instructions
WB50_60-11:FE4105
Page 35
The correct configuration of the parameters above is absolutely necessary to
guarantee optimum operation with generators from different manufacturers.
Preconditions for changing the operating parameters are described in chapter 6.4
"General setting example” (page 37).
Name
WB 5000
WB 6000
Unit
Description
UpvStart
300
(250 ... 600)
300
(250 ... 600)
V
DC
Defines the voltage at the
moment when the Windy
Boy 5000 / 6000 is ready to
perform a mains supply
synchronization.
UdcWindStart 330
(1 ... 800)
330
(1 ... 800)
V
DC
Defines the voltage at the
moment when the Windy
Boy 5000 / 6000 is ready to
begin feeding power into the
mains supply.
UdcWindMax 550
(1 ... 800)
550
(1 ... 800)
V
DC
Defines the voltage at the
moment when the Windy
Boy 5000 / 6000 begins
feeding maximum power
into the mains supply.
P-Wind-Ramp
500
(10 ... 2000)
500
(10 ... 2000)
W/sec
Controls a delayed startup
of the characteristic curve,
only after the Windy Boy
5000 / 6000 has been
switched on. This avoids the
generator being suddenly
presented with a heavy
load.
T-Start
10
(5 ... 1600)
10
(5 ... 1600)
sec
Start Timer Mains
synchronization.
T-Stop
2
(1 ... 3600)
2
(1 ... 3600)
sec
Stop Timer Aborting the
supply of power and
switching off.
To perform the configuration process, the DC input voltage must be greater
than
mains supply.