beautypg.com

2 critical, faulty operation, 3 non-critical, faulty operation, Critical, faulty operation – SMA WB 5000 User Manual

Page 18: Non-critical, faulty operation

background image

Unit description

SMA

Technology AG

Page 18

WB50_60-11:FE4105

Operating instructions

3.3.2 Critical, faulty operation

A comprehensive safety concept limits the number of critical conditions that can occur
to a single situation:

Input voltage exceeds the permitted value

This is indicated by the following blink-code on the yellow LED:

The yellow fault LED illuminates for 5 seconds when the fault occurs, and then begins
displaying the blink code of: 3 seconds off and then 4 times briefly on. This code is
displayed three times in succession. If the fault is still present, the fault display starts
again from the beginning

.

3.3.3 Non-critical, faulty operation

All other fault codes indicate some form of faulty operation, which are not usually
dangerous to people or equipment, but which should nevertheless be investigated
and corrected.

Despite all precautions, it is possible that other faults may occur that cannot be
displayed (e.g. failure of the status display). In order to recognize such faults, the
operator of the system should use the explanations in chapter 3.3.4 "Description of
the operational status” (page 19)
to check the plausibility of the displayed status.
Further detailed diagnoses are possible using the communications options detailed in
chapter 8 "Expansions” (page 41).

The presence of excessive input voltage can lead to irreparable
damage! Immediately disconnect the DC input of the Windy Boy
5000 / 6000.

When the Windy Boy 5000 / 6000 receives an excessive DC input voltage, it
automatically disconnects from the mains supply and no longer feeds power
into the grid. When the Windy Boy 5000 / 6000 is in operation, you must
always first disconnect the AC voltage (mains supply) and only then should you
disconnect the DC voltage from the Windy Boy 5000 / 6000!

5 s

3 s

1 s

1 s

1 s

1 s

LED on

LED off

The message is repeated 3 times
and then begins again.

1

2

3

4

The yellow LED
illuminates 4 times

This manual is related to the following products: