Technical Data
Installation Manual
SB25-30-IA-en-51
67
Protective Devices
General Data
Overvoltage category according to IEC 60664-1
III
Maximum cable length at conductor cross-section
of 2.5 mm²
12.5 m
DC reverse polarity protection
Short-circuit diode
Input-side disconnection device
Electronic Solar Switch
DC overvoltage protection
Thermally monitored varistors
AC short-circuit current capability
Current control
Mains monitoring
SMA Grid Guard 2.1
Maximum permissible fuse protection
16.0 A
Earth fault monitoring
Insulation monitoring: R
iso
> 1 M Ω
Galvanic isolation
Available
Width x height x depth with Electronic Solar Switch
440 mm x 339 mm x 214 mm
Weight
32 kg
Length x width x height of packaging
532 mm x 392 mm x 318 mm
Transport weight
36.6 kg
Climatic category according to IEC 60721-2-1
4K4H
Operating temperature range
− 25°C … +60°C
Maximum permissible value for relative humidity,
non-condensing
100%
Maximum operating altitude above MSL
2 000 m
Noise emission (typical)
≤ 30 dB(A)
Power loss in night operation
≤ 0.25 W
Topology
LF transformer
Cooling concept
Convection
Electronics degree of protection according to
IEC 60529
IP65