beautypg.com

9 troubleshooting, 1 blink codes, Troubleshooting – SMA SB 2500 Installation User Manual

Page 51: Blink codes

background image

SMA Solar Technology AG

Troubleshooting

Installation Manual

SB25-30-IA-en-51

51

9 Troubleshooting

If the inverter displays other blink codes or error messages than those described below, contact the
SMA Service Line.
You will also find a description of display messages during operation, status messages and
measurement channels in the user manual provided.
Do not perform any repairs that are not described here and take advantage of the 24-hour
replacement service (inverter ready for shipping and handed over to a freight-forwarding company
within 24 hours) and the SMA Solar Technology AG repair service instead.

9.1 Blink Codes

Green

Red

Yellow

Status

Flashing

Flashing

Flashing

OK (startup phase)

Is permanently lit

Is not lit

Is not lit

OK (feed-in operation)

Is permanently lit

Is not lit

Earth fault or varistor defective

Is permanently lit

OK (initialisation)

Flashing quickly
(3 x per second)

Is not lit

Is not lit

OK (stop)

Is permanently lit

Is not lit

Earth fault or varistor defective

Flashing slowly
(1 x per second)

Is not lit

Is not lit

OK
(waiting, mains monitoring)

Is permanently lit

Is not lit

Earth fault or varistor defective

Goes out briefly
(approx. 1 x per second)

Is not lit

Is not lit

OK (derating)

Is permanently lit

Is not lit

Earth fault or varistor defective

Is not lit

Is not lit

Is not lit

At night: OK
(overnight shutdown)
During the day:
Electronic Solar Switch is not
attached

Is lit/flashing

Fault

Is permanently lit

Is not lit

Earth fault or varistor defective

Is lit/flashing

Earth fault or varistor defective
and fault