background image

Opening and Closing

SMA Solar Technology AG

44

SB33-38-11-IA-en-62

Installation Manual

4. Connect the AC plug.

5. If an external DC switch-disconnector is present, disconnect the external DC switch-

disconnector.

6. If an Electronic Solar Switch is present, check the

Electronic Solar Switch for wear as described in
section 8.3 "Checking the Electronic Solar Switch
for Wear" (page 49) an
d reattach firmly.

7. Switch on the miniature circuit-breaker.
8. Check whether the inverter's display and LED

display indicate a normal operating state
(see section 6 "Commissioning" (page 39)).

☑ The inverter is closed and in operation.

NOTICE!
Damage to the inverter due to moisture and dust intrusion

If the Electronic Solar Switch is not plugged in or incorrectly plugged in during operation,
moisture and dust can penetrate the inverter.
If the Electronic Solar Switch is not correctly plugged in, this can cause contacts to wear in
the Electronic Solar Switch or the Electronic Solar Switch might fall down. This can result in
yield loss and damage to the Electronic Solar Switch.
Always plug in the Electronic Solar Switch as described in the following:

• Do not tighten the screw in the Electronic Solar Switch.
• Firmly plug in the Electronic Solar Switch until it is flush with the enclosure.
• Ensure that the maximum distance between the Electronic Solar Switch and the

enclosure is 1 mm.