beautypg.com

SMA SB 3300 Installation User Manual

Page 67

background image

SMA Solar Technology AG

Technical data

Installation Guide

SB33_38-IEN111851

67

Mechanical Data

Climatic Conditions

* according to DIN EN 50178:1998-04, installation type C, class 4K4H
** according to DIN EN 50178:1998-04, transport type E, class 2K3

Features

General Data

* according to DIN EN 60529

Protective Devices

Width x height x depth

450 mm x 352 mm x 236 mm

Weight

38 kg

Extended temperature range*

− 25 °C … +60 °C

Extended air humidity range*

0 % … 100 %

Extended air pressure range*

79.5 kPa … 106 kPa

Temperature range**

− 25 °C … +70 °C

Operating temperature range

− 25 °C … +60 °C

Maximum operating altitude above mean sea
level

2 000 m

Topology

LF transformer

Cooling concept

OptiCool

Fan connection

Designed for safe disconnection

In accordance with DIN EN 60529

Protection rating*

IP65

Protection class

I

Noise emission (typical)

≤ 40 dB(A)

All-pole DC disconnection unit

Electronic Solar Switch,

DC plug system SUNCLIX

DC overvoltage protection

Thermally monitored varistors

Personal protection (R

iso

> 1 M Ω )

Insulation monitoring

Reverse polarity protection

Short circuit diode

AC short circuit protection

Current control

All-pole AC disconnection unit

Automatic disconnection device

SMA Grid Guard 2.1