Troubleshooting

Installation Guide

SB33_38-IEN111851

61

You can check the functionality of the varistors in the following manner:

1. Open the inverter as described in section 7.2 ”Opening the Inverter” (page 43).
2. Use a multimeter to ensure that all of the varistors in

the installed state have a conducting connection
between connectors B and C.

Result

Measure

☑ There is a conducting connection. There is probably a different fault in the inverter.

• Close the inverter as described in section

7.3 ”Closing the Inverter” (page 45).

• Contact the SMA Serviceline (see section

13 ”Contact” (page 73)).

☑ There is no conducting

connection.

The respective varistor is defective and must be replaced.
Varistor is generally due to influences that affect all
varistors similarly (temperature, age, induced
overvoltage). SMA Solar Technology AG recommends
replacing all varistors.
The varistors are specially manufactured for use in
inverters and are not commercially available. You must
order replacement varistors directly from SMA Solar
Technology AG (see section 12 ”Accessories”
(page 72)).

• To replace the varistors, proceed to step 3.

NOTICE!
Destruction of the inverter due to overvoltage.

If varistors are missing, the inverter is no longer protected against overvoltages.

• Provide for replacement varistors immediately and replace the faulty varistors.
• For systems with a high risk of overvoltage, do not operate inverters with faulty

varistors or no varistors at all.