Troubleshooting

SMA Solar Technology AG

56

SB33_38-IEN111851

Installation Guide

Shutdown

Temporary inverter disturbance.
Corrective measures

• Contact the SMA Serviceline.

Trafo-Temp-F

Temperatures in the transformer have exceeded the acceptable limit.
The inverter stops feeding the grid until the temperature lies within the
acceptable range.
Corrective measures

• If this problem recurs, check the heat dissipation of the inverter, as

described in section 8.1 ”Checking Heat Dissipation” (page 47).

Trafo-Temp-W

Temperatures in the transformer have exceeded the acceptable limit. The
inverter stops feeding the grid until the temperature lies within the
acceptable range. The Trafo-Temp-W warning is displayed until final
shutdown (at the end of the day).
Corrective measures

• Check the heat dissipation of the inverter, as described in section

8.1 ”Checking Heat Dissipation” (page 47).

Vac-Bfr
Vac-Srr

The grid voltage on line 2 is no longer within the permissible range ("Bfr"
or "Srr" is an internal message that has no meaning for the user). This
code can be caused by any of the following conditions:

• Grid disconnected (line circuit breaker, fuse),
• AC cable is broken or
• AC cable is highly resistive

For safety reasons, the inverter disconnects itself from the grid.
Corrective measures

• Check the grid current and grid connection on the inverter.
• If the grid voltage lies outside the acceptable range because of

local grid conditions, ask the electric power company if the
voltages can be adjusted at the feed-in point or if they agree to
changes in the values of the monitored operational limits (operating
parameters: Vac-Min and Vac-Max).

• If the grid frequency is within the tolerable range, yet "Vac-Bfr", or

"Vac-Srr" faults are still being displayed, please contact the
SMA Serviceline.