beautypg.com

SMA SB 3300 Installation User Manual

Page 19

background image

SMA Solar Technology AG

Assembly

Installation Guide

SB33_38-IEN111851

19

7. If a second protective conductor is not required,

secure the inverter against excavation:
– Insert cylinder bolt with safety washer through

the metal lashing eye on the bottom of the
enclosure. The toothing of the safety washer
must face toward the metal shackle.

– Tighten cylinder bolt to a tightening torque of

6 Nm.

8. Check to ensure that the inverter is firmly fastened. The wall mounting bracket is designed so

that the inverter tilts backward slightly on a perfectly vertical wall.

9. Attach the ventilation grids provided to the inverter.

To help you identify the sides, "links/left" or "rechts/
right" is printed on the inside of the ventilation grids.

☑ The inverter is now mounted.