beautypg.com

SMA SB 3300 Installation User Manual

Page 57

background image

SMA Solar Technology AG

Troubleshooting

Installation Guide

SB33_38-IEN111851

57

Vpv-Max

Overvoltage at DC input. The inverter could be damaged.
Corrective measures
Immediately disconnect the inverter from the grid.

1. Turn off the line circuit breaker.
2. Remove the Electronic Solar Switch.
3. Disconnect all the DC connectors.
4. Check DC voltage:

– If the DC voltage exceeds the maximum input voltage, check the

plant design or contact the person who installed the PV
generator.

– If the DC voltage is below the maximum input voltage,

reconnect the inverter to the PV generator as described in
section 5.5.4 ”Connecting the PV Generator (DC)” (page 33).

If the message appears again, disconnect the inverter again and contact
the SMA Serviceline (see section 13 ”Contact” (page 73)).

Watchdog
Watchdog-Srr

Internal program run fault.

Corrective measures

• If this fault continues to occur, contact the SMA Serviceline.

Zac-Bfr
Zac-Srr

The grid impedance is no longer within the permissible range
("Bfr" or "Srr" is an internal message of no relevance for the user).
For safety reasons, the inverter disconnects itself from the grid. The
impedance is calculated from both the grid impedance and the
impedance of the AC cable of the inverter.
Corrective measures

• Check the grid impedance and grid connection on the inverter.
• Use an AC cable with an adequate cross-sectional area

(= low impedance) as described in section 5.3 ”Connection to the
Power Distribution Grid (AC)” (page 22).
If required, check and re-
tighten the screws on the AC terminals.

• If this fault recurs, contact the SMA Serviceline.

Message

Description and Corrective Measure

This manual is related to the following products: