Rating for a line circuit breaker

Installation Guide

SB700-11:SA2006

Page 47

Summary:

The selected line circuit breaker can be used in our example case since the maximum
current-carrying capacity for fault-free operation is higher than the maximum output
current of the inverter used. It will trip under rated operating conditions!

If the calculated current-carrying capacity of the circuit breaker had been lower than
the maximum output current from the inverter, the following solution might have been
used:

By spacing the circuit breakers at an interval of 8 mm, the reduction factor would be
0.98 instead of 0.77. As a result, the maximum current-carrying capacity would
increase to 9.4 A.

As well as the thermal rating of the circuit breakers and all other factors as specified
in section "Rating for a line circuit breaker in a photovoltaic electrical power unit
operated in parallel with the low-voltage grid" (page 16)
, of course the applicable
DIN VDE standards

1

also need to be taken into account. The main ones that apply

here are:

• DIN VDE 0100; part 410
• DIN VDE 0100; part 430
• DIN VDE 0298; part 4

In special applications the relevant standards must be followed.

1. The standards mentioned above are to be only used as a guideline for your

installation. They apply for installations in Germany. Please note that other
standards will apply for different countries throughout the world.