5 operating parameters, Operating parameters – SMA SB 700 User Manual
Page 39
SMA
Technologie AG
Technical data
Installation Guide
SB700-11:SA2006
Page 39
7.5 Operating parameters
The parameters with a grey background are only visible when in installer mode.
Unauthorised changes to the operating parameters may result
in:
• Injury or accidents as a result of changing the internal
safety routines in the Sunny Boy
• Voiding the Sunny Boy's operating approval certificate
• Voiding the Sunny Boy's guarantee
Never change the parameters of your Sunny Boy without
express authorization and instructions.
Name
Unit
Value range
Factory setting
Betriebsart /
Operating mode
MPP, IKonst, UKonst, Stopp, Turbine
Mode, Insel Mode
MPP
Default
GER/ENS
dFac-Max
Hz/s
0.005 ... 4.0
0.5
dZac-Max
mOhm
0 ... 20000
350
E_Total
kWh
0 ... 200000
Fac-Delta-
Hz
0 ... 4.5
0.19
Fac-Delta+
Hz
0 ... 4.5
0.19
h_Total
h
0 ... 200000
I-NiTest /
Testcurrent Zac
mA
0 ... 6000
4500/
4000/
3500
Speicherfunktion /
Memory function
Default Parameter, Reset Betriebsdaten,
Reset Fehler
none
Speicher/Storage
Permanent, volatile
Permanent
T-Start
s
5 ... 300
10
T-Stop
s
1 ... 3600
2
Uac-Min / Vac-Min
V
180 ... 300
198
Uac-Max / Vac-Max
V
180 ... 300
260
Upv-Start /
Vpv-Start
V
125 ... 250/
100 ... 200/
75 ... 150
150/
125/
95
Usoll-Konst /
Vconst-Setpoint
V
125 ... 330/
100 ... 330/
75 ... 330
275/
275/
275