7.5 Operating parameters

The parameters with a grey background are only visible when in installer mode.

Unauthorised changes to the operating parameters may result
in:

• Injury or accidents as a result of changing the internal

safety routines in the Sunny Boy

• Voiding the Sunny Boy's operating approval certificate
• Voiding the Sunny Boy's guarantee

Never change the parameters of your Sunny Boy without
express authorization and instructions.

Name

Unit

Value range

Factory setting

Betriebsart /

Operating mode

MPP, IKonst, UKonst, Stopp, Turbine

Mode, Insel Mode

MPP

Default

GER/ENS

dFac-Max

Hz/s

0.005 ... 4.0

0.5

dZac-Max

mOhm

0 ... 20000

350

E_Total

kWh

0 ... 200000

Fac-Delta-

Hz

0 ... 4.5

0.19

Fac-Delta+

Hz

0 ... 4.5

0.19

h_Total

h

0 ... 200000

I-NiTest /

Testcurrent Zac

mA

0 ... 6000

4500/
4000/

3500

Speicherfunktion /

Memory function

Default Parameter, Reset Betriebsdaten,

Reset Fehler

none

Speicher/Storage

Permanent, volatile

Permanent

T-Start

s

5 ... 300

10

T-Stop

s

1 ... 3600

2

Uac-Min / Vac-Min

V

180 ... 300

198

Uac-Max / Vac-Max

V

180 ... 300

260

Upv-Start /

Vpv-Start

V

125 ... 250/
100 ... 200/

75 ... 150

150/
125/

95

Usoll-Konst /

Vconst-Setpoint

V

125 ... 330/
100 ... 330/

75 ... 330

275/