7.3 Input voltage range 73 ... 150 V DC
7.3.1 PV generator connection data
7.3.2 Grid connection data
Max. input open circuit voltage
U
PV 0
250 V (based on -10 °C cell
temperature)
Input voltage, MPP range
U
PV
73 V ... 150 V
Max. input current
I
PV m ax
7 A
Max. input power
P
D C
510 W
Recommended generator power
600 Wp
All-pole isolator on the DC input side
DC plug connector
Overvoltage protection
Thermally monitored varistors
Voltage ripple
U
pp
< 10 % of the input voltage
Insulation protection
Ground fault monitoring
(Riso > 1 MΩ)
Operating consumption
< 4 W (standby)
Reverse polarity protection
Short circuit diode
Nominal output power
P
AC nom
460 W
Peak output power
P
AC m ax
460 W
Nominal output current
I
AC nom
2 A
Harmonic distortion of output current
(at K
U grid
< 2 %, P
AC
> 0.5 P
AC nom
)
K
IAC
< 3 %
Short-circuit strength
Grid-side via current regulation
Operating range, grid voltage
U
AC
198 ... 260 V AC
Operating range, grid frequency
f
AC
49.8 ... 50.2 Hz
All-pole isolation on grid side
Independent disconnection device
(MSD), redundant design
Phase shift angle (based on the current's
fundamental frequency)
cos ϕ
1
Overvoltage category
III
Test voltage (50 Hz)
1.3 kV (1 s routine testing / 5 s type
testing)
Test surge voltage
4 kV (serial interface: 6 kV)
Own consumption in night mode
0.1 W