Installation requirements

SMA

Technologie AG

Page 16

SB700-11:SA2006

Installation Guide

Rating for a line circuit breaker in a photovoltaic electrical
power unit operated in parallel with the low-voltage grid

Various factors should be taken into account when selecting line circuit breakers.
These include, for example:

• The type of cable used (conductor material and insulation)
• Ambient temperatures affect the cables (higher temperatures result in a reduced

maximum current load)

• Method of routing the cable (reduces the ampacity of the conductor)
• Bundling cables together (reduces the ampacity of the conductor)
• Loop impedance [Z] (in the event of a body contact this limits the current that can

flow and therefore determines the response behaviour of the circuit breaker)

• Adequate clearance between the circuit breakers in order to avoid excessive

heating (automatic circuit breakers trip earlier when they are warmer)

• Selectivity
• Protection class of the connected load (VDE 0100, part 410), Protection against

electric shock

The following standards

1

should be followed in all cases:

• DIN VDE 0298-4

(Cable routing and current-carrying capacity)

• DIN VDE 0100; part 430

(Protective measures; protection of cable and

cords against overcurrent)

• DIN VDE 0100; part 410

(Protective measures; protection against electric

shock)

We recommend using a 16 A line circuit
breaker to protect the power circuit. No
loads should be connected to this power
circuit.

Please have a look at chapter 9 "Rating for a line circuit breaker" (page 45).

1. The standards mentioned above are to be only used as a guideline for your

installation. They apply for installations in Germany. Please note that other
standards will apply for different countries throughout the world.

16A

Betrieb
Operation

Erdschluss
Earth Fault

Störung
Failure

Photovoltaik-Stringwechselrichter
Photovoltaic string inverter