beautypg.com

SMA SIC 50 User Manual

Page 43

background image

SMA Solar Technology AG

Technical Data

Installation Guide

SIC50-IA-en-11

43

SIC50-MPT

Efficiency / Power consumption
Max. efficiency

98 %

Euro-Eta

97.3 %

Self-consumption during the day

< 5 W @ U

Bat nom

= 48 V

DC

Internal consumption at night

< 3 W @U

Bat nom

= 48 V

DC

General
Dimensions (W x H x D)

421 mm x 310 mm x 143 mm

Protection rating according to IEC 60529

IP65

Weight

10 kg

Device protection

short circuit / reverse polarity / overload /

overvoltage and undervoltage / overtemperature

and undertemperature

EC Declaration of Conformity

download area www.SMA.de/en

Display

1 x multicolored LED

Mounting type

suspended

Configuration

plug & play in combination with Sunny Island

(CAN Piggy-Back required) DIL switch with stand-

alone applications and in SMA operation

Parallel operation

up to four devices through CAN bus

Battery temperature compensation

-4 mV/°C

Interfaces

CAN Piggy-Back (optional)

External temperature sensor

KTY type (optional)

Ambient conditions
Permissible ambient temperature during
operation

–25 °C … +60 °C

Air humidity

0 % ... 100 %

Altitude (operational)

5 000 m above mean sea level

Transport height

16 000 m above mean sea level