SMA SIC 50 User Manual
Page 43
SMA Solar Technology AG
Technical Data
Installation Guide
SIC50-IA-en-11
43
SIC50-MPT
Efficiency / Power consumption
Max. efficiency
98 %
Euro-Eta
97.3 %
Self-consumption during the day
< 5 W @ U
Bat nom
= 48 V
DC
Internal consumption at night
< 3 W @U
Bat nom
= 48 V
DC
General
Dimensions (W x H x D)
421 mm x 310 mm x 143 mm
Protection rating according to IEC 60529
IP65
Weight
10 kg
Device protection
short circuit / reverse polarity / overload /
overvoltage and undervoltage / overtemperature
and undertemperature
EC Declaration of Conformity
download area www.SMA.de/en
Display
1 x multicolored LED
Mounting type
suspended
Configuration
plug & play in combination with Sunny Island
(CAN Piggy-Back required) DIL switch with stand-
alone applications and in SMA operation
Parallel operation
up to four devices through CAN bus
Battery temperature compensation
-4 mV/°C
Interfaces
CAN Piggy-Back (optional)
External temperature sensor
KTY type (optional)
Ambient conditions
Permissible ambient temperature during
operation
–25 °C … +60 °C
Air humidity
0 % ... 100 %
Altitude (operational)
5 000 m above mean sea level
Transport height
16 000 m above mean sea level