beautypg.com

11 failure search, 1 sma operation, 2 stand-alone operation – SMA SIC 50 User Manual

Page 40: Failure search, Sma operation, Stand-alone operation

background image

Failure Search

SMA Solar Technology AG

40

SIC50-IA-en-11

Installation Guide

11 Failure Search

11.1 SMA Operation

You can find the description of all parameters and errors in the Sunny Island manual.

11.2 Stand-alone Operation

You can read the error messages through the serial interface using the terminal program. The device
number is shown as x in the following.

Error code

Description

Ex=+0000.0

no error

Ex=+0000.2

DC input voltage missing
(also at night and during periods with low solar irradiation)

Ex=+0000.4

overvoltage at DC input voltage

Ex=+0000.8

battery temperature too high or sensor cable interrupted

Ex=+0001.6

battery temperature too low or short circuit in the sensor cable

Ex=+0003.2

charge controller temperature is higher than 90 °C

Ex=+0006.4

battery temperature is lower than -30 °C

Ex=+0012.8

battery voltage is lower than 8.1 V

Ex=+0025.5

short circuit, overload or overcurrent at battery or PV array
(also before first commissioning)