(First) Commissioning

Installation Guide

SIC50-IA-en-11

35

7.1.2 Battery System

The battery system is set using the C1, C2 and C3 DIL switches. The following table displays the switch
position of the required battery system.

7.1.3 Device Address

The sequential order of the devices is determined by configuring the device address. The device
address is set using the D1, D2 and D3 DIL switches.

The following table displays the switch position of the device addresses:

Switch

12 V battery system

24 V battery system

48 V battery system

C1

ON

OFF

OFF

C2

OFF

ON

OFF

C3

OFF

OFF

ON

Stand-alone operation
In the "Stand-alone operation" mode, the device address must be set to 0.

SMA operation
In the "SMA operation" mode, up to four charge controllers may be connected to the
Sunny Island. The device addresses intended for these four devices are one to four.

Device address

D3

D2

D1

0

OFF

OFF

OFF

1

OFF

OFF

ON

2

OFF

ON

OFF

3

OFF

ON

ON

4

ON

OFF

OFF

5

ON

OFF

ON

6

ON

ON

OFF

7

ON

ON

ON