Electrical Connection

SMA Solar Technology AG

20

SIC50-IA-en-11

Installation Guide

6.3 Grounding

6.3.1 Grounding the Charge Controller

1. Open the charge controller. Loosen the screws of the enclosure lid and remove the lid.
2. Unscrew the lock nut of the metric-thread cable

gland (B) and slide it along the PE cable.

3. Route the PE cable through the cable gland into the

charge controller and connect it to the "EARTH"
connection terminal (A).

4. Retighten the lock nut of the cable gland.

N

M25 metric-thread cable gland for the signaling contact and the battery temperature
sensor cables

O

M25 metric-thread cable gland for communication cable

DANGER!
Risk of lethal electric shock.

The charge controller has the protection class I.

• Ground the charge controller properly, regardless of whether the battery and PV are

grounded.