Error

EEPROM

Transition failure during reading or writing of data EEPROM,
the data is not essential for safe operation - this failure does
not effect performance.

Error

EEPROM p

Data EEPROM defective, device is set to permanent disable
due to the fact that the data loss affects important functions of
the inverter. Contact SMA for assistance.

Error

OFFSET

Grid monitoring self-test failed. Contact SMA for assistance.

Error

ROM

The internal test of the Sunny Boy control system firmware
failed. Contact SMA for assistance.

Error

Watchdog

Watchdog for operation control triggered. Contact SMA for
assistance.

Error

Bfr-Srr

Communication between micro-controllers is failing. Contact
SMA for assistance.

Error

Shut-Down

Internal over current continuous. Contact SMA for assistance.

Error

EarthCur-
Max-S

The earth current between PV+ and GND has exceeded the
maximum limit. Check the PV array for ground faults.

Error

EarthCur-
Max-B

The earth current between PV+ and GND has exceeded the
maximum limit. Check the PV array for ground faults.

Error

GFDI Fuse
Ope

The GFDI-Fuse is open or cleared. Check the PV array for
ground faults before replacing the fuse.

Error

Derating

The inverter is derating because of high temperature. Verify
that the fans are operating normally and that the intake
screens are clean. Check the intake vents for debris. Verify
that there is adequate ventilation around the inverter. This
condition may be normal in periods of high ambient temper-
atures (above 45°).

Error

XFMR_TEMP
_F

High transformer temperature. The inverter will remain
stopped until the transformer has cooled.

Error

XFMR_TEMP
_W

High transformer temperature is gone. The SB3800U starts
working and shows the failure “XFMR_TEMP_W“. Verify that
the fans are operating normally and that the intake screens
are clean. Check the intake vents for debris. Verify that there
is adequate ventilation around the inverter. This condition
may be normal in periods of high ambient temperatures
(above 45°).

Error Type

Error Code

Description