Displays and Messages

SB3800U-12:SE2006

SMA America

7-19

SB3800U Operating Parameters

CAUTION: The changing of operating parameters should only
be performed by qualified personnel. Changes to factory preset
parameters may adversely effect inverter operation and perfor-
mance.

Table 7-1 Operating Parameters of the SB3800U

Name

Unit

Range

Default

Password

Level

Description

E_Total

kWh

0 ... 200000

0

Total energy yield (E_Total) and
total operating hours (h_Total) of the
inverter. Changing the value can be
necessary when a Sunny Boy is
exchanged and you wish to match
the previously acquired data.

h_Total

h

0 ... 200000

0

Vconst-Setval

V

500

PV Setpoint voltage for constant
voltage operation. These
parameters only are important in
case the parameter “Operating
Mode“ is set to “V-const“.

Vpv-Start

V

.8 ... 2x VAC
nominal

264 V @
240 V AC,
229 V @
208 V AC

Minimum DC voltage for the Sunny
Boy to connect to the grid. Set using
formula, for example, default value
for 240 is 1.099 x 240 = 264.
Formula can be adjusted from 0.8 to
2.0 x nominal V.

T-Start

s

5 ... 1600

10 / 300

The time the inverter waits to
connect to the grid after Vpv-Start is
exceeded.

This value defaults to 5 minutes after
a utility fault.

T-Stop

s

1 ... 1800

2

The time that the Sunny Boy waits to
disconnect from the grid when Pac
falls below 10W.

T-Stop-Fan

degC
(°C)

0 ... 100

50

Fan turn-off temperature

T-Start-Fan

degC
(°C)

0 ... 100

60

Fan turn-on temperature at
minimum rotating speed.

T-Max-Fan

degC
(°C)

0 ... 100

90

Temperature for maximum fan
rotation speed.

Fan-Test

1 / 0

0

By setting this parameter to “1“ you
can check the function of the fans.
This test turns the fans at maximum
speed.