SMA SB 3800-U User Manual
Page 68

Displays and Messages
7-20
SMA America
SB3800U-12:SE2006
The following parameters appear in parameter list but cannot be modified:
Table 7-2 Operating Parameters of the Sunny Boy 3800U (Fixed)
Operating Mode
MPP-Operation
Turbine
V-const
Stop
MPP-
Mode
Operating Modes of the Sunny Boy:
MPP-Operation: Maximum Power
Point
V-const: Constant Voltage Mode
(Setpoint defined in “Vconst-
Setval“)
Turbine: Operating mode for wind
power plants
Stop: Disconnection from utility, no
operation
Memory Function
no function
Default param.
Reset Op.Data
Reset errors
no
function
Default param.: Sets all parameters
to default.
Reset Op.Data: Sets all parameters
that are visible in user level to
default values.
Reset errors: Resets all permanent
device disable errors.
Name
Unit
Range
Default
Description
Plimit
W
3800
Upper limit of AC output power
SMA-SN
Serial Number of the Sunny Boy
Software-BFR
Firmware version of the operation control unit (BFR)
Software-SRR
Firmware version of the current control unit (SRR)
Hardware-BFS
Hardware version of the DC converter control unit
(DC-BFR)
Vac-Min
%
Fixed
12
Lower and upper limits of allowable AC voltage
Vac-Max
%
Fixed
10
Fac-delta-
Hz
Fixed
0.69
Maximum allowable operating frequency above
and below 60 Hz
Fac-delta+
Hz
Fixed
0.49
dFac-MAX
Hz/s
Fixed
0.5
Maximum “rate of frequency change” before anti-
islanding protection engages
Default
Fixed
USA/
UL1741/
2001
Used for adjusting the parameters country specific
settings.
Name
Unit
Range
Default
Password
Level
Description