beautypg.com

Led fault indicators -6, Led fault indicators – SMA SB 3800-U User Manual

Page 54

background image

Displays and Messages

7-6

SMA America

SB3800U-12:SE2006

LED Fault Indicators

Ground Fault

The inverter has detected a ground fault in the PV system and has disconnected from the
grid. The ground fault must be located and fixed before the inverter will resume
normal operation.

The inverter will not restart automatically. Refer to Section 8:

“Troubleshooting” for information on solving PV array ground faults.

Note:

All GFDI faults are disabled in turbine mode.

Cleared GFDI Fuse

The GFDI fuse located in the fuse holder on the bottom of the inverter has been cleared
or is not present. This fuse is used to protect the PV system in the event of an array
ground fault. Troubleshoot the PV array for ground faults prior to replacing this fuse.

CAUTION: For continued protection against the risk of fire,
replace the GFDI fuse with fuses of the same type and rating
only. The SB3800U is shipped with a Littelfuse KLKD 1 Amp,
600V AC/DC

type fuse.

Red LED is on

Yellow LED is on

Red LED is on