RS-485 Communication

RS-485 is a communication standard for bidirectional transmission of data between one

or more Sunny Boy inverters and a PC.

Note:

All Sunny Boy inverters are capable of RS-485

communication. You can mix different Sunny Boy models on the

RS-485 communication bus.

Requirements for RS-485 Communication:

• The Sunny Boy 3800U must be equipped with an RS-485 Piggy-Back communica-

tion module.

• The cable should be no longer than 1200 meters (4000 feet) with a common shield,

and a wire size no smaller than 24 AWG. Use the cable type specified in the RS-
485 Tech Note on www.sma-america.com.

• RS-485 cables are available from SMA America.

• Conduit may be required for communication wiring, per local electrical code re-

quirements.

Connecting an RS-485 Cable

Use the following procedure to install an RS-485 data-communication network:

Note:

The following steps describe how to connect one or

more Sunny Boy inverters to an RS-485 bus. For more

information on connecting more than one inverter to an RS-

485 bus, please see “Technical Note: RS-485

Communication” in the Tech Updates section of our web site

at www.sma-america.com

1. Connect the three wires of the RS-485 cable to terminals 2, 5, and 7 of the

communication terminal block as shown in Figure 5-8. Record the wire color used

for each of the terminals. Two communication knockouts are provided for

connecting multiple Sunny Boys on an RS-485 communication bus.

2. Connect the shield of the cable to the Sunny Boy 3800U’s case. (See Figure 5-8)

Do NOT connect the cable shield to the PC’s DB-9 connector. The shield must

remain floating at the PC.

3. Install a jumper in position A, the bottom set of pins on the communication jumper

block, to set it for termination. (See Figure 5-8)