Percent voltage drop for 208 V AC and 240 V AC service

Figure 5-2 Energy Losses in Various Wire Sizes and Wire Lengths

The SB3800U is designed to automatically detect which grid voltage it is feeding if a
neutral is connected to the inverter. Depending upon the voltage and phase angle
between L1-N and L2-N, the inverter will determine if it is connected to a 208 V or 240
V grid. Table 5-1 lists the voltage and frequency limits for the AC connection.

Table 5-1 Voltage and Frequency Limits for the AC Connection

Voltage Range for 208 V nominal, line to line

183 V - 229 V

Voltage Range for 240 V nominal, line to line

211 V - 264 V

Frequency Range

59.3 Hz - 60.5 Hz

0,0%

One way distance (feet)

20

40

80

120

160

200

240

0,4%

0,8%

1,2%

1,6%

2,0%

Percent of 208 V AC and 240 V AC

60

100

0

140

180

220

8 AWG

6 AWG

10 AWG

12 AWG