SMA STP 15000TL User Manual

Page 53

background image

Grid configurations

TN-C, TN-S, TN-C-S, TT (when V

N_PE

< 30 V)

Approvals and national standards, as per
10/2014*

AS 4777, BDEW 2008, C10/11:2012, CE,

CEI 0-16, CEI 0-21, EN 50438, G59/3,

IEC 60068-2, IEC 61727, MEA/PEA,

IEC 62109-2, NEN 50438, PPC, PPDS,

RD 1699, RD 661/2007, SI4777,

UTE C15-712-1, VDE 0126-1-1, VDE AR-

N 4105, VFR 2013, VFR 2014

* C10/11:2012: only possible if the three-phase line-to-line voltage is 400 V.

EN 50438: does not apply to all national appendices of EN 50438.
IEC 62109-2: This standard requires that either the multifunction relay in the inverter is used as fault
indicator or that the inverter is connected to Sunny Portal and that the fault alert is activated in
Sunny Portal.
NRS 97-2-1: This standard requires a separate label be attached to the AC distribution board to
indicate the AC-side disconnection of the inverter in case of a grid failure (for further details, see
NRS 97-2-1, Sect. 4.2.7.1 and 4.2.7.2).
MEA/PEA: only applicable to STP 17000TL-10

Climatic Conditions

Installation in accordance with IEC 60721-3-3, Class 4K4H

Extended temperature range

-25°C to +60°C

Extended humidity range

0% to 100%

Extended air pressure range

79.5 kPa to 106 kPa

Transport in accordance with IEC 60721-3-2, Class 2K3

Temperature range

-25°C to +70°C

Electronic Solar Switch

Electrical endurance in the event of short circuit,
at nominal current of 33 A

At least 50 switching operations

Maximum switching current

33 A

Maximum switching voltage

1,000 V

Maximum power

 20 kW

Degree of protection when plugged in

IP65

Degree of protection when unplugged

IP21

Features

DC Connection

SUNCLIX DC connector

AC connection

Spring-cage terminal

Display

LC graphic display

11 Technical Data

SMA Solar Technology AG

Operating Manual

53

STP15-17TL-10-BE-en-10