9.

Damage to the inverter due to moisture ingress
The inverter is only properly sealed when all unused DC inputs are closed with DC connectors
and sealing plugs.

• Do not insert the sealing plugs directly into the DC inputs on the inverter.
• For unused DC connectors, push down the

clamping bracket and push the swivel nut
up to the thread.

• Insert the sealing plug into the DC

connector.

• Tighten the DC connector (torque: 2 Nm).

• Insert the DC connectors with sealing plugs

into the corresponding DC inputs on the
inverter.

☑ The DC connectors snap into place.

10. Remove the ESS.

☑ The display switches off.