Battery Cabinet Precautions

The following warning applies to all battery cabinets supplied with UPS systems. Additional warn-

ings and cautions applicable to battery cabinets may be found in 3.0 - Battery Installation.

!

CAUTION

This equipment is fitted with RFI suppression filters.
Ground leakage current exceeds 3.5 mA and is less than 1000 mA.
Transient and steady-state ground leakage currents, which may occur when starting the

equipment, should be taken into account when selecting instantaneous residual current

circuit breakers (RCCBs) or residual current devices (RCDs).
RCCBs must be selected sensitive to DC unidirectional pulses (Class A) and insensitive to

transient current pulses.
Note also that the ground leakage currents of the load will be carried by this RCCB or RCD.

!

WARNING

Under typical operation and with all UPS doors closed, only normal safety precautions are

necessary. The area around the UPS system should be kept free of puddles of water, excess

moisture and debris.
Special safety precautions are required for procedures involving handling, installation and

maintenance of the UPS system and the battery. Observe all safety precautions in this

manual before handling or installing the UPS system. Observe all precautions in the

Operation and Maintenance Manual, before as well as during performance of all maintenance

procedures. Observe all battery safety precautions before working on or near the battery.
This equipment contains several circuits that are energized with high voltage. Only

test equipment designed for troubleshooting should be used. This is particularly true for

oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making

contact or using tools. Even when the power is turned Off, dangerously high electric charges

may exist within the UPS.
All power and control wiring should be installed by a qualified electrician. All power

and control wiring must comply with the NEC and applicable local codes.
ONLY qualified service personnel should perform maintenance on the UPS system.

When performing maintenance with any part of the equipment under power, service

personnel and test equipment should be standing on rubber mats. The service personnel

should wear insulating shoes for isolation from direct contact with the floor (earth ground).
Never work alone, even if all power is removed from the equipment. A second person should

be standing by to assist and summon help in case an accident should occur.

!

CAUTION

This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J

of the FCC rules. These limits provide reasonable protection against harmful interference in a

commercial environment. This unit generates, uses and radiates radio frequency energy and,

if not installed and used in accordance with this instruction manual, may cause harmful

interference to radio communications. This unit is not designed for use in a residential area.

Operation of this unit in a residential area may cause harmful interference that the user must

correct at his own expense.

!

WARNING

Internal battery strapping must be verified by manufacturer prior to moving a battery cabinet

(after initial installation).
• Battery cabinets contain non-spillable batteries.
• Keep units upright.
• Do not stack.
• Do not tilt.
Failure to heed this warning could result in smoke, fire or electric hazard.
Call 1-800-LIEBERT before moving battery cabinets (after initial installation).