Table 35 maintenance bypass cabinet dimensions, Table 35, Maintenance bypass cabinet dimensions – Emerson 60HZ User Manual

Page 76: Table 36, Multi-module paralleling cabinet dimensions, Table 37, Distance to connection points on the nx ups

background image

Specifications and Technical Data

70

8.2

Cable Lengths: Floor to Connection Point Inside UPS

To help calculate the total cable length required, refer to Table 37 for the distance from the floor to

selected connection points inside the NX. Determine the cable length required to reach the NX, then

add the appropriate length from the table and adequate slack for repair and maintenance.

Table 35

Maintenance bypass cabinet dimensions

Unit

Width

Depth

Height

inch

27.2

31.4

63

mm

690

825

1600

Table 36

Multi-module paralleling cabinet dimensions

1+1 Cabinet Type

Width

Depth

Height

1+N Narrow

27.2

31.4

63

Types A00, BR0, CR1, DR1

690

825

1600

1+N Cabinet Type

Width

Depth

Height

1+N Narrow

27.2

31.4

63

Types A00, E00, J00

690

825

1600

1+N Wide

58.5

31.4

63

All other types

1488x

825x

1600

Table 37

Distance to connection points on the NX UPS

Connection Point on UPS

Distance

From

Floor

in. (mm)

From

Top of Unit

in. (mm)

Bypass AC input supply

30 (750)

30 (750)

UPS output AC

30 (750)

30 (750)

Neutral busbars—Input and Output

11 (280)

55 (1397

Battery power

16 (400)

58 (1474)

Auxiliary cables: Monitor board (U2)

60 (1500)

20 (508)

Communications

55 (1400)

25 (635)

Ground

8 (197)

56 (14227)

Parallel Board

70(1780)

20(508)