Table 29, Tables 29 – Emerson 60HZ User Manual
Page 66
Specifications and Technical Data
60
Table 29
Maintenance bypass cabinet electrical data (single input)
kVA Type
Maintenance
Bypass
I/P Voltage
(VAC)
Bypass Cabinet
Max Input
Current
Cabinet
Input OCP
CB Size (A)
O/P Voltage
(VAC)
Nominal O/P
Current Rating (A)
Output
OCP CB Size (A)
30
A, J
208
104
125
208
83
125
30
B, K
480
47
60
208
83
125
30
B, K
600
37
50
208
83
125
30
B, K
220
101
125
208
83
125
30
C, L
480
48
60
480
36
50
30
C, L
600
38
50
600
29
40
30
C, L
220
105
125
220
79
100
30
D, M
480
47
60
208
83
125
30
D, M
600
38
50
208
83
125
30
D, M
208
108
150
208
83
125
30
D, M
220
103
125
208
83
125
30
D, M
240
93
125
208
83
125
30
E, N
480
48
60
480
36
50
30
E, N
600
39
50
600
29
40
30
E, N
220
106
125
220
79
100
20
A, J
208
69
90
208
56
70
20
B, K
480
31
40
208
56
70
20
B, K
600
25
30
208
56
70
20
B, K
220
68
90
208
56
70
20
C, L
480
32
40
480
24
30
20
C, L
600
26
40
600
19
30
20
C, L
220
70
90
220
52
70
20
D, M
480
31
40
208
56
70
20
D, M
600
25
40
208
56
70
20
D, M
208
72
90
208
56
70
20
D, M
220
68
90
208
56
70
20
D, M
240
62
80
208
56
70
20
E, N
480
32
40
480
24
30
20
E, N
600
26
40
600
19
30
20
E, N
220
70
90
220
52
70
15
A, J
208
52
70
208
42
60
15
B, K
480
23
30
208
42
60
15
B, K
600
19
30
208
42
60
15
B, K
220
51
70
208
42
60
15
C, L
480
24
30
480
18
30
15
C, L
600
19
30
600
14
20
15
C, L
220
52
70
220
39
50
15
D, M
480
23
30
208
42
60
15
D, M
600
19
30
208
42
60
15
D, M
208
54
70
208
42
60
15
D, M
220
51
70
208
42
60