Electrical Connections

11

2.1.4 Cable Connections

The rectifier input, bypass and output are easily accessible from the left side of the unit for installa-

tion. All require lug type terminations. They are connected to busbars on the left side of the NX and

below the switch, as shown in Figure 3. These busbars are accessible when the left side panel is

removed. Busbars to connect external batteries are accessible from the front of the UPS.

Figure 3

Input busbars

The internal batteries are connected with Anderson connectors inside the battery compartment. The

batteries are connected to fuses to protect the NX and connected equipment (see Figure 4).

Figure 4

Battery fuses and connections

NOTE
External battery connection access requires removal of a protective panel on the lower front of

the UPS to the left of the bottom two battery shelves.

C

B

OUTPUT

BYPASS

A

C

B

A

Rectifier Input

Busbars

(Phases are

indicated by

letters below the

bars)

Output Busbars

(Phases are

indicated by

letters below the

bars)

Remove these links

for dual input

configuration and

wire UPS Main input

directly to CB1

Bussmann

MADE IN USA

150A 500V AC/DC

B

Bussmann

MADE IN USA

150A 500V AC/DC

B

Internal battery input

connections

Battery fuses

(fuses are behind

access plate on

front of UPS; see

Note on page 11)