4 ups electrical characteristics, Table 10 ups terminal, Ups electrical characteristics – Emerson 60HZ User Manual
Page 45: Table 10, Ups terminal, Table 10 , wit, In table 10, To table 10, 4 - ups electrical characteristics, Ratings in table 10 . for

UPS Specifications
39
6.4
UPS Electrical Characteristics
Table 10
UPS terminal
Input (for single-input unit)
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Current
OCP
Device
Rating
Bolt Size
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
10
28
35
42
45
6M (1/4”)
54105
62204
15
42
53
63
70
6M (1/4”)
54106
62204
20
56
70
84
90
6M (1/4”)
54107
62204
30
83
104
125
125
6M (1/4”)
54152
62205
Rectifier input (for dual input unit only)
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Current
OCP
Device
Rating
Bolt Size
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
10
25
31
37
40
6M (1/4”)
54130
62204
15
37
47
57
60
6M (1/4”)
54106
62204
20
50
63
76
80
6M (1/4”)
54107
62204
30
75
94
113
125
6M (1/4”)
54152
62205
Bypass input (for dual input units)
Unit
Rating
Nominal
Input
Current
OCP
Current
OCP
Device
Rating
Bolt Size
Maximum Recommended Lug
Lug T&B
One Hole
54000
Lug T&B
One Hole
REDDY
10 28 35 35
6M
(1/4”)
54105 62204
15 42 53 60
6M
(1/4”)
54106 62204
20 56 70 70
6M
(1/4”)
54107 62204
30 83
104 110
6M
(1/4”)
54152 62205
Output
Unit
Rating
Nominal
Output
Current
OCP
Current
OCP
Device
Rating
Bolt Size
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
10
28
35
35
6M (1/4”)
54130
62204
15
42
53
60
6M (1/4”)
54106
62204
20
56
70
70
6M (1/4”)
54106
62204
30
84
105
110
6M (1/4”)
54108
62205
Battery
Unit
Rating
Battery
Current
OCP
Current
OCP
Device
Rating
Bolt Size
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
10/15
55
55
70
6M (1/4”)
54106
62204
20/30
110
110
125
8M (5/16”)
54153
62212