0 ups specifications, 1 conformity and standards, 2 ups environmental – Emerson 60HZ User Manual
Page 44: Table 8 environmental characteristics, 3 ups mechanical characteristics, Table 9 mechanical characteristics, Ups s, Pecifications, Conformity and standards, Ups environmental
UPS Specifications
38
6.0
UPS S
PECIFICATIONS
These specifications describe requirements for the Liebert NX UPS.
6.1
Conformity and Standards
The UPS has been designed to conform to the following standards:
• IEEC1000-4-5
• ASME
• CSA 22.2, No. 107.1
• FCC Part 15, Class A
• ISO 9001
• National Electrical Code (NFPA-70)
• NEMA PE-1
• OSHA
• UL Standard 1778
The UPS system has UL and c-UL approval.
6.2
UPS Environmental
The UPS is designed to operate under the following environmental conditions without damage or deg-
radation in electrical operating characteristics:
6.3
UPS Mechanical Characteristics
Table 8
Environmental characteristics
Rated Power
10-30kVA
Operating Temperature, UPS
32°F to 104°F (0°C to 40°C)
Optimal Operating Temperature, Battery
68°F to 86°F (20°C to 30°C)
Relative Humidity
0 to 95%, non-condensing
Acoustical Noise, dBA at 39 in. (1m)
54
Altitude of Operation
≤1000m per IEC 62040/3
Storage-Transport Temperature, UPS
-4°F to 158°F (-20°C to 70°C)
Storage-Transport Temperature, Battery
-4°F to 86°F (-20°C to 30°C)
Table 9
Mechanical characteristics
Parameter
10kVA
15kVA
20kVA
30kVA
Width, in. (mm)
24 (600)
Depth, in. (mm)
32.5 (825)
Height, in. (mm)
63 (1600)
Weight Without Inner Batteries, lb. (kg)
450 (205)
450 (205)
550 (250)
550 (250)
UPS12-100 weight
954 (433)
954 (433)
1054 (478)
1054 (478)
UPS12-140 weight
1098 (498)
1098 (498)
1198 (543)
1198 (543)
Heat Dissipation, BTU/H (kWH)
2800 (0.82)
4200 (1.23)
5500 (1.61)
8300 (2.43)
Airflow, CFM (m
3
/h)
384 (652)
558 (948)
522 (886)
834 (1417)
Cable Entry
Bottom or top
Color
PMS 877
Protection Grade (with open/closed front doors)
IP 20