beautypg.com

Cable management guidelines – H3C Technologies H3C SecPath F5000-S Firewall User Manual

Page 82

background image

73

Cable management guidelines

When you route and bundle up cables, follow these guidelines:

Bind and route the cables neatly inside the rack, and make sure that the cables are not kinked or
bent.

Figure 51 Correct and incorrect cable binding

The cable bend radius at connectors must be at least 5 times the cable diameter, and must be at

least twice the cable diameter away from the connectors.

Route different types of cables (for example, power cables, and signal cables) separately. If they are
close to one another, cross them over one another. If you route them in parallel, make sure that the

space between a power cable bundle and a signal cable bundle is at least 30 mm (1.18 in).

The cable management brackets and cable routing slots, inside or outside the rack, are smooth and
have no sharp edges or tips.

When you route cables through sharp sheet metal penetration points or along sharp edges of
mechanical parts, use bushings or take any other action to protect the cables from being cut or

abraded. The sheet metal penetration points must be smooth and fully rounded.

Use the correct ties to bind the cables. Do not bind cables with joined ties. The following types of

ties are available: 100 × 2.5 mm (3.94 × 0.10 in), 150 × 3.6 mm (5.91 × 0.14 in), 300 × 3.6 mm
(11.81 × 0.14 in), 530 × 9 mm (20.87 × 0.35 in), and 580 × 13 mm (22.83 × 0.51 in).

After binding the cables, cut the excess from the ties, leaving no sharp or angular tips. See

Figure

52

.

This manual is related to the following products: