beautypg.com

Connecting the grounding cable to the switch – H3C Technologies H3C S3100V2 Series Switches User Manual

Page 35

background image

29

CAUTION:

The supplied grounding cable of the S3100V2 Switch Series does not have an auxiliary OT terminal.

Connect the grounding cable to the earthing system in the equipment room. Do not connect it to a fire
main or lightning rod.

Connecting the grounding cable to the switch

Follow these steps to connect the grounding cable to the switch:

Step1

Remove the grounding screw on the rear panel of the switch.

Step2

Attach the OT terminal on the grounding cable to the grounding screw on the chassis.

Step3

Fasten the grounding screw, which is attached with the OT terminal of the grounding cable, into the

grounding screw hole with a screwdriver.

Figure 38 Connect the grounding cable to the switch

(1) Switch rear panel

(2) Grounding sign

(3) Grounding hole

(4) OT terminal

(5) grounding cable

(6) Grounding screw

Connecting the grounding cable to a grounding strip

Follow these steps to connect the grounding cable to a grounding strip:

Step1

Remove the hex nut from the grounding strip.

Step2

Cut the grounding cable to a proper length according to the distance between the switch and the

grounding strip.

Step3

Make the connector on the grounding cable:

If you have an OT terminal, follow callout A in

Figure 39

to make the connector: Peel 5 mm (0.20

in) of insulation sheath by using a wire stripper, and then insert the naked metal part through the
insulation covering into the end of the OT terminal. Secure the metal part of the cable to the OT

terminal with a crimper, and then cover it with the insulation covering. Then heat the insulation

covering with a blower to make it completely cover the metal part.

If you do not have an OT terminal, follow callout B in

Figure 39

to make the connector: Peel the

insulation sheath by an appropriate length by using a wire stripper, and then bend the naked metal