15.6 Calibrate the pump for 4-20mA control
This feature is only available in the Universal+ model.
The pump must be stopped before attempting to calibrate the 4-20mA values.
High and low signals must be within range. If the signal sent is out of range you will
not be able to set the signal input value and progress to the next step in the process.
Select MODE.
Using the +/- keys scroll to Analog 4-20mA and press CALIBRATE 4-20mA.
Choose whether to enter the current values manually via the keypad, or whether to
apply the current signals electrically to the analogue input.
Setting a high signal
Send the high signal input to the pump, or enter the current value using the +/-
keys.