beautypg.com

Users manual, Mc100, 5 process status bits from the pumps – Watson-Marlow MC100 User Manual

Page 22

background image

Users Manual

MC100

MC100 DeviceNet OM 1.15 EN

Version: 1.04

Page 22 of 43

7.1.5 Process status bits from the pumps


To retrieve status from each pump, one byte (8 bits) is dedicated as described below.

Minimum one word is received with status from the pumps. The number of pumps connected is a
parameter, which is part of the configuration of the number of cyclic bytes of the network.
The MC100 will always automatically send the number of bytes for the connected pumps, after a
factory reset to defaults.

Word 8

Word 7

Word 6

Word 5

Word 4

Word 3

Word 2

Word 1

P16 P15 P14 P13 P12 P11 P10

P9

P8

P7

P6

P5

P4

P3

P2

P1


Bit mapping in the status byte:

7

6

5

4

3

2

1

0

ALARM

Direction

DONE

Pump

Dispense Tube Br.

BUSY

READY


Bit 0:

READY

Pump is ready (self check is OK).

Bit 1:

BUSY

“1” Indicate that the pump is active, either dispensing or pumping

“0” pump is idle

Bit 2:

Tube Br.

Tube bridge bit:

”1” = tube bridge on,

“0” = tube bridge off.

Bit 3:

Dispense

Dispense bit:

“1” = dispense mode

Bit 4:

Pump

Pump bit:

“1” = pump mode

Bit 5:

DONE

4

Set, when pump goes from dispensing to idle / reset by a new START bit.

Bit 6:

Direction

Handshake for bit B5 from command byte (0=normal / 1=reverse direction.)

Bit 7:

ALARM

See Chapter 8 for further information


4

The DONE bit can be necessary to use if there is very short filling times, where the BUSY signal is not detected because of

transmission times on the fieldbus network.