7.1.4 Process control bits for the pumps


To control each pump one byte (8 bits) is dedicated as described below.

Minimum one word is transmitted for pump control. The number of pumps connected is a parameter,
which is part of the configuration of the number of cyclic bytes of the network.

Word 8

Word 7

Word 6

Word 5

Word 4

Word 3

Word 2

Word 1

P16 P15 P14 P13 P12 P11 P10

P9

P8

P7

P6

P5

P4

P3

P2

P1


Bit mapping in each command byte:

7

6

5

4

3

2

1

0

Direction

Disable in

Par./Serial

RESET

PUMP

DISP

START


Bit 0: START

Starts a single Dispense cycle, when the Pump is set in Dispense mode (Bit. 1)
This bit must be cleared upon receiving the BUSY bit in the status byte for the
pump, see below.

Bit 1: DISP

Sets the pump in dispense mode and thereby enables the START bit to start
dispenses. If removed during a dispense, the pump stops immediately.

Bit 2: PUMP

2

Starts pump running continuously with the speed set in ADI 3.

Bit 3:

Reserved for future use

Bit 4: RESET

To be used with future pumps

Bit 5:

Disable pump in parallel and serial mode.

Bit 6: Direction

3

[1/0] [Backwards/Normal] pump and dispense direction.

Bit 7

Reserved for future use

2

The DISP bit has higher priority and must be cleared before setting the PUMP bit.

3

Available for pumps able to handle this function (GD30).