Initial installation – Enviro Haven Direct Vent Fireplace User Manual

Page 22

background image

Figure 32. Vent Framing Through Wall/Ceiling.

Figure 31. Vent Pipe Clearances.

2" (51mm)

7

11

/

16

" (195mm)

39"

(991mm)

Initial Installation

QUALIFIED INSTALLERS ONLY

V

ENTING

:

This fireplace has been tested and certified for use with SIMPSON DURAVENT DIRECT VENT TYPE “GS”

PIPE FOR GAS STOVES, SECURITY CHIMNEY’S SECURE VENT DIRECT VENT SYSTEM kits, AMERICAN

METAL PRODUCTS AMERIVENT DIRECT and DIRECT-TEMP SELKIRK METALBESTOS.
A 1” (25 mm) clearance to combustibles must be maintained around any vertical vent pipe. Around a

horizontal vent pipe, the clearance to combustibles should be 2” (51 mm) above and 11⁄2” (38 mm) on

the sides and bottom. When combustible materials are directly above a 90° elbow, 3 inches (7.6 cm) of

clearance are necessary (see Figure 31).

Table 6. Vent Pipe Minimum Clearances.

Vertical Pipe to

the Side Walls

Horizontal Pipe to

the Sides & Bottom

Above an Elbow

Above the Unit

Above an Elbow

Not Above the Unit

Above Horizontal

Vent Pipe

Wall Frame 8”

(203mm) or less

Hard

Pipe

1”

(25.4 mm)

11⁄2”

(38.1 mm)

7

11

/

16

(195mm)

3”

(76.2 mm)

2”

(51 mm)

10”x10”

(25x25cm)

Flex

Pipe

1”

(25.4 mm)

11⁄2”

(38.1 mm)

7

11

/

16

(195mm)

3 3⁄8”

(86 mm)

3 3⁄8”

(86 mm)

10”x10”

(25x25cm)

A 10” (254 mm) x 10” (254 mm) frame (see Figure 32) will assure the proper support and spacing for

the vent pipe as it passes through the wall. Installations in Canada require that a wall thimble be used

for passing through walls and ceilings. All sealing and vapour barriers must comply with local building

codes.

When planning an installation, it is necessary to select the proper length

of vent pipe for the particular requirements. The configuration of the

venting pipes depends on the locations of walls, ceilings and studs.

However, the pipes cannot be of arbitrary length and arrangement.

Because the length of the vertical and horizontal sections dramatically

affects the burning efficiency of the fireplace, certain guidelines have

been set in I

NITIAL

I

NSTALLATION

- V

ENT

C

ONFIGURATIONS

AND

R

ESTRICTOR

S

ETTINGS

.

Venting terminals can not be recessed into a wall or siding.
WARNING: This gas appliance must not be connected to a

chimney flue serving a separate solid-burning appliances.

22