Initial installation – Enviro Haven Direct Vent Fireplace User Manual
Page 15
15
Initial Installation
QUALIFIED INSTALLERS ONLY
Figure 20. Top Mounting brackets.
F
RAMING
M
OUNT
B
RACKETS
:
Figure 17. Raised Fireplace with Floor Level
Hearth.
Figure 18. Raised Fireplace with Raised Hearth.
18" (457mm)
minimum to
ceiling
Figure 19. Raised Fireplace with No Hearth.
The Haven can be secured to the framing and
the flooring. At either side of the top there
are two (2) brackets with holes for screws or
nails (Figure 20); the back tabs are to mount
to the wood framing and the front ones are to
mount to the drywall. At the bottom there are
two (2) mounting holes in the unit base below
the firebox, which allows for screws or nails to
mount to the floor (Figure 21).